Alpitronic charging stations

Alpitronic

Supported Devices

Device TypeVariantsModbus TCP (Ethernet)RS485
Alpitronic HYCHYC50, HYC150, HYC300, HYC400
Image 1

Configuration

External control of the charging station must be activated in the configuration menu via the web page of the charging station. To do this:

  1. Surf to the IP address and log in with the default data or your own set of data (default user = admin, default password = admin123).
  2. In the settings of the charging station:
    1. Go to "General"
    2. Go to "Power"
    3. Set "ModBus Enabled" to "True"
    4. Click on "Save Settings"
Image 1
Image 1
  1. "Grid Fallback Timeout" is the maximum time allowed between 2 commands from the Sofar EMS. The default is 5 seconds, set this to 60 seconds by default. Afterward, click "Save Settings" again
Image 1
  1. Activate the changes by Resetting the charging station.
    1. Go to the main page
    2. Check that no cars are connected to the charging station
    3. Go to "Reset"
    4. Click on "Soft Reset HYC"
Image 1