Afore

Supported Devices

Device TypeModbus TCP (Ethernet)RS485Curtailment
Single Phase (1-3kW)
Single Phase (3-6kW)
Single Phase (7-10kW)
Three Phase (3-25kW)
Three Phase (30kW)
Three Phase (36-60kW)
Three Phase (70-110kW)

Specific Models

Device TypeModbus TCP (Ethernet)RS485Curtailment
AF1-3.6K-SL-1
AF3-3.6K-SL
AF4-6K-SLP
AF1-6K-SL-0
AF3-9.6K-DH
AF3-15K-MTH
AF3-30K-TH
AF36-50K-TH
AF3-12K-THP
AF3-30K-TH-0
AF3-12K-THP-0

Configuration

1. Accessing the Inverter's Interface

  1. Power On the Inverter

    • Ensure the inverter is powered and operational
  2. Navigate to the Main Menu

    • Use the inverter's display panel to access the main menu

2. Locating Communication Settings

  1. Enter the Settings Menu

    • From the main menu, select 'Settings' or 'Advanced Settings'
  2. Find Communication Options

    • Look for options labeled 'Communication', 'RS485', or 'Modbus'

3. Configuring Modbus Parameters

  1. Set Communication Protocol

    • Choose 'Modbus RTU' as the protocol
  2. Adjust Communication Parameters

    ParameterValue
    Baud Rate9600 or 19200 bps
    ParityNone or Even
    Data Bits8
    Stop Bits1
  3. Assign Modbus Address

    • Provide a unique slave ID (e.g., 1, 2, etc.) for the inverter