Supported Devices
warning
The GoodWe only supports RS485 connection. No Modbus TCP support is available.
Device Type | Modbus TCP (Ethernet) | RS485 | Curtailment |
---|---|---|---|
ES Series | ❌ | ✅ | ❌ |
S-BP Series | ✅ | ||
HT Series | |||
MT Series | |||
KT Series | |||
DT Series | |||
SMT Series | |||
EH Series | |||
ET Series | |||
BT Series | |||
BH Series |
Configuration
1: Connecting the RS485
1a Connect the RS485 strings between the GoodWe inverter and the Eniris controller. As you may see on this scheme, you coult connect the

2: SolarGo Settings
Step | Image |
---|---|
2a. Connect to the inverter’s WiFi and open the SolarGo app. | ![]() |
2b. Click More. | ![]() |
2c. Click Advanced Setting (you can find the password in the SolarGo manual). | ![]() |
2d. Select Grid Parameter Setting. | ![]() |
2e. Turn off Power Limit (If it is on, power from the battery cannot be fed into the grid). | ![]() |
2f. Go back and click Cancel (these settings will be saved anyway, no restart is needed). | ![]() |
3: Battery Settings in SolarGo.
Step | Image |
---|---|
3a. Select Battery Setting. | ![]() |
3b. Turn off SOC Protection. | ![]() |
3c. Go back and click Cancel (these settings will be saved anyway, no restart is needed). | ![]() |
TCP Connection
It has been reported to work with GoodWe ET, EH, BT, BH, ES, EM, BP, DT, MS, D-NS, and XS families of inverters but this is not supported.
Wiring
If you have multiple goodwe devices it is possible to change adresses seperately for each device. Or you can daisy chain them. (https://docs.eniris.be/wiring-best-practices/#wiring)