Przejdź do głównej zawartości

Autarco LH-series RS485 wiring

logo

This page describes the communication with an Autarco LH-series hybrid inverter over Modbus-RTU (rs485). By default, the inverter is set to address 1. The RS485 interface is a 4-pin connector called "COM" located on the bottom of the inverter behind a protective plate. The exact position is marked in the orange box in the image below:

Image

Looking closer the port looks like this:

Image

An appropriate connector should be used for this 4-pin connector on the Autarco inverter to connect to the Sofar EMS. On the Sofar EMS, the inverter can be connected to the RS485 port. The wiring is as follows:

RS485 Wiring
  • For correct RS485 wiring: Follow the guidelines for RS485 wiring.
  • If the wiring shown in the table below is incorrect, please let us know.
  • There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
DeviceSofar EMS model OM1Sofar EMS model IG8RS485-USB converterRS485-Ethernet converter
Pin 3 RS485 ARS485_POSRS485 ATX+
Pin 4 RS485 BRS485_NEGRS485 BTX-
N/A RS GNDGNDNot availableG
NOTE: RS485 Device Addresses
  • You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
  • Use lower addresses first (1, 2, ...) because the Sofar EMS will find them faster!
  • For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The Sofar EMS will scan on those first.