Autarco MH-series RS485 wiring

This page describes the communication with an Autarco LH-series hybrid inverter over Modbus-RTU (rs485). By default, the inverter is set to address 1. The RS485 interface is a 4-pin connector called "COM" located on the bottom of the inverter behind a protective plate. The exact position is marked in the orange box in the image below:

Looking closer the port looks like this:

An appropriate connector should be used for this 4-pin connector on the Autarco inverter to connect to the Sofar EMS. On the Sofar EMS, the inverter can be connected to the RS485 port. The wiring is as follows:
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
Device | Sofar EMS model OM1 | Sofar EMS model IG8 | RS485-USB converter | RS485-Ethernet converter |
---|---|---|---|---|
Pin 3 | RS485 A | RS485_POS | RS485 A | TX+ |
Pin 4 | RS485 B | RS485_NEG | RS485 B | TX- |
N/A | RS GND | GND | Not available | G |
NOTE: RS485 Device Addresses
- You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
- Use lower addresses first (1, 2, ...) because the Sofar EMS will find them faster!
- For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The Sofar EMS will scan on those first.