عدادات سوليس للطاقة
الأجهزة المدعومة
| Device Type | Modbus TCP (Ethernet) | RS485 |
|---|---|---|
| Solis Energy Meter | ✅ | ✅ |
| Autarco Energy Meter |
الاتصال
إيثرنت
للتوصيل الصحيح لكابل الإيثرنت: اتبع إرشادات توصيل إيثرنت.
RS485
معلومات
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
| Device | Sofar EMS model OM1 | Sofar EMS model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| A | RS485 A | RS485_POS | RS485 A | TX+ |
| B | RS485 B | RS485_NEG | RS485 B | TX- |
| GND (optional) | RS GND | GND | Not available | G |
التكوين
تحذير
NOTE: RS485 Device Addresses
- You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
- Use lower addresses first (1, 2, ...) because the Sofar EMS will find them faster!
- For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The Sofar EMS will scan on those first.
تأكد من أن العداد مُكوَّن بالإعدادات التالية في بروتوكول Modbus لتتوافق مع مواصفات برنامج التشغيل:
- معدل البود: 9600
- بتات البيانات: 8
- بتات التوقف: 1
- التكافؤ: لا شيء
- عنوان Modbus: 1 (الافتراضي) - النطاق: 1 إلى 254