Start generating reactive power above (kVAr): When the imported grid reactive power rises above this value, the inverters will start producing reactive power to limit the grid reactive power to this value.
Stop generating reactive power below (kVAr): When the imported grid reactive power drops below this value, the inverters will stop producing reactive power.
Stop consuming reactive power above (kVAr): When the imported grid reactive power rises below this value, the inverters will stop consuming reactive power.
Start consuming reactive power below (kVAr): When the exported grid reactive power goes below this value, the inverters will start consuming reactive power to limit the grid reactive power to this value.
The reactive power peak shaving settings are similar to the settings for peak shaving of active power.
Tip
Tip
Reactive power compensation
To aim towards complete reactive power compensation, set all the reactive power peak shaving settings to zero.