Schneider-Electric IEM 2100-serien energimätare
Stödda enheter
IEM 2100-serien är enfas energimätare.
| Device Type | Modbus TCP (Ethernet) | RS485 |
|---|---|---|
| Schneider-Electric iEM 2100 Series | ❌ | ✅ |
| Schneider-Electric iEM 2150 | ||
| Schneider-Electric iEM 2155 |

Anslutning
IEM 2100-serien kommunicerar via Modbus RTU över RS485.
Info
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
| Device | Sofar EMS model OM1 | Sofar EMS model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| D1 (+) | RS485 A | RS485_POS | RS485 A | TX+ |
| D0 (-) | RS485 B | RS485_NEG | RS485 B | TX- |
| 0V / Shield | RS GND | GND | Not available | G |
Vänligen se enhetens manual för exakta pinplaceringar, då dessa kan variera något mellan specifika undermodeller (t.ex. iEM2150 vs iEM2155).
Konfiguration
Varning
NOTE: RS485 Device Addresses
- You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
- Use lower addresses first (1, 2, ...) because the Sofar EMS will find them faster!
- For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The Sofar EMS will scan on those first.
Kommunikationsinställningar
Säkerställ att enhetens inställningar matchar drivrutinens kapabiliteter enligt nedan:
- Baud Rate: 9600, 19200 eller 38400 (Standard är ofta 19200)
- Paritet: Jämn, Udda eller Ingen
- Stopbitar: 1
- Databitar: 8
Kontrollera enhetens manual för hur man går in i energimätarens konfigurationsmeny för att ställa in Modbus-adress och Baud Rate.