iWell Cube-batteri
Stödda enheter
| Device Type | Variants | Modbus TCP (Ethernet) | RS485 | Curtailment |
|---|---|---|---|---|
| iWell Cube Battery (Experimental) | Cube Series | ✅ | ❌ | ✅ |

Koppling
Sofar EMS kommunicerar med iWell Cube-batterisystemet via Modbus TCP (Ethernet).
Anslut Ethernet (LAN)-porten på batterisystemet till samma nätverk som Sofar EMS.
Info
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
| Device | Sofar EMS model OM1 | Sofar EMS model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| Ethernet (TCP/IP) Port | RS485 A | RS485_POS | RS485 A | TX+ |
| Port Number | RS485 B | RS485_NEG | RS485 B | TX- |
| Connection Type | RS GND | GND | Not available | G |
Tips
Tips
Säkerställ att både Sofar EMS och iWell Cube-batteriet finns i samma IP-subnät
(t.ex. 192.168.1.xxx) och kan kommunicera via port 1025.
Varning
Varning
iWell Cube:s Modbus TCP-gränssnitt är aktivt endast när batterisystemet är påslaget och initialiserat.
Anslut inte till inaktiva enheter eller under firmwareuppdateringar.