The peak shaving relay cascade is a special local control mode that is implemented to switch relays in specific order on or off for peak shaving. This works similar to a last-in-first-out (LIFO) queue.
This can be used to control the grid power to remain between the on and off thresholds, with on/off loads.
The order of the relays is determined by:
For each of the relays that are controlled, it is recommended to set the 'Use case' to 'Switching a device or circuit' in the device settings page. You should also set the 'Default device state' to whatever is desirable in case there is a problem with the control mode.
Minimum & maximum switch on and wait times: Timing related device settings are ignored in the peak shaving relay cascade control mode. You can however configure a debounce time between switching on and off when enabling the control mode.
See Special local control modes for the priority towards other signals, and for pausing or removing the mode.