Metcom Energy Meters
In beta and available on request. The additions in this overview require the matching integration or controller update and are not confirmed as part of the standard customer release. Request them through your existing Eniris support conversation. The status applies to these additions, not to every existing function of the devices listed elsewhere on this page.
| Model / system | Beta addition | Validation and conditions |
|---|---|---|
| Metcom Blue2box | Signed import/export power | Import positive; export negative |
See integration details for connection requirements and operating limitations.
| Device Type | Modbus TCP (Ethernet) | RS485 |
|---|---|---|
| Metcom MCS301 | ✅ | ✅ |
| Metcom Blue2box | ❌ |
For correct ethernet wiring: Follow the the guidelines for ethernet wiring.
| Device | Sofar EMS model OM1 | Sofar EMS model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| A | RS485 A | RS485_POS | RS485 A | TX+ |
| B | RS485 B | RS485_NEG | RS485 B | TX- |
| N/A | RS GND | GND | Not available | G |
View the manual for more information on configuration.
View the manual for more information. The energy meter uses the DLMS/COSEM broadcast protocol, so it should not be necessary to set an address.
Blue2box monitoring reports exported active power as negative and imported active power as positive.