Pilot Energy Meters
| Device Type | Modbus TCP (Ethernet) | RS485 |
|---|---|---|
| Pilot SPM33 | ✅ | ✅ |
The RS485 terminals are located on the back of the device.
| Device | Sofar EMS model OM1 | Sofar EMS model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| 13 (A+) | RS485 A | RS485_POS | RS485 A | TX+ |
| 12 (B-) | RS485 B | RS485_NEG | RS485 B | TX- |
| 14 (Shield) | RS GND | GND | Not available | G |
Power Supply Ensure the device is powered using terminals 1 (L/+) and 3 (N/-). The auxiliary power supply range is AC 85-265V or DC 100-300V.
Use the following Modbus settings in the EMS's device wizard. These are the default settings for the meter: