Medidores de Energía Solis
Dispositivos compatibles
| Device Type | Modbus TCP (Ethernet) | RS485 |
|---|---|---|
| Solis Energy Meter | ✅ | ✅ |
| Autarco Energy Meter |
Conexión
Ethernet
Para un cableado ethernet correcto: siga las .
RS485
Info
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
| Device | Sofar EMS model OM1 | Sofar EMS model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| A | RS485 A | RS485_POS | RS485 A | TX+ |
| B | RS485 B | RS485_NEG | RS485 B | TX- |
| GND (optional) | RS GND | GND | Not available | G |
Configuración
Advertencia
NOTE: RS485 Device Addresses
- You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
- Use lower addresses first (1, 2, ...) because the Sofar EMS will find them faster!
- For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The Sofar EMS will scan on those first.
Asegúrese de que el medidor esté configurado con los siguientes ajustes Modbus para que coincidan con las especificaciones del controlador:
- Baudrate: 9600
- Bits de datos: 8
- Bits de parada: 1
- Paridad: Ninguna