Schneider-Electric PM 5000 Series Energy Meters
The PM 5000 series covers a wide range of meters. Capabilities vary by specific model number (e.g., PM51xx are generally RS485 only, while PM5320/PM5340 include Ethernet).
| Device Type | Modbus TCP (Ethernet) | RS485 |
|---|---|---|
| Schneider-Electric PM 5100 / 5110 / 5111 | ❌ | ✅ |
| Schneider-Electric PM 5310 / 5330 / 5331 | ||
| Schneider-Electric PM 5320 / 5340 / 5341 | ✅ |
pm5300
Applicable only to PM5320, PM5340, and PM5341. For correct ethernet wiring: Follow the guidelines for ethernet wiring.
The RS485 terminals are located on the bottom of the device (connector 6 in the diagram below).
| Device | Sofar EMS model OM1 | Sofar EMS model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| Terminal 22 / D1 (+) | RS485 A | RS485_POS | RS485 A | TX+ |
| Terminal 23 / D0 (-) | RS485 B | RS485_NEG | RS485 B | TX- |
| Terminal 25 / 0V | RS GND | GND | Not available | G |
Shielding: The shield wire should be connected to Terminal 24 (SHLD). Note that the ground terminal is not available on the meter itself; the shield should be connected to ground at the other end of the bus[cite: 246, 1627].
Applicable only to PM5320, PM5340, and PM5341. To configure the IP address:
To configure the Serial settings (Baud rate, Parity, ID):