Solis Energy Meters
| Device Type | Modbus TCP (Ethernet) | RS485 |
|---|
| Solis Energy Meter | ✅ | ✅ |
| Autarco Energy Meter |
For correct ethernet wiring: Follow the the guidelines for ethernet wiring.
InfoRS485 Wiring
- For correct RS485 wiring: follow the RS485 wiring guidelines.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general industry consensus on the use of A and B for RS485 polarity, so the naming may be counterintuitive for some devices.
WarningNOTE: RS485 Device Addresses
- You MUST give each device a unique address on the RS485 bus. Check the device manual for instructions.
- Use lower addresses first (1, 2, ...) because the Sofar EMS will find them faster!
- For each device, it is generally recommended to keep the factory-default baud rate, parity, and stop bits. The Sofar EMS will scan those first.
Ensure the meter is configured with the following Modbus settings to match the driver specifications:
- Baudrate: 9600
- Data bits: 8
- Stop bits: 1
- Parity: None
- Modbus Address: 1 (default) - Range: 1 to 254