Schneider-Electric IEM 2100 Serie Energietellers
Ondersteunde Apparaten
De IEM 2100 Series zijn enkelfase energieverbruikmeters.
| Device Type | Modbus TCP (Ethernet) | RS485 |
|---|---|---|
| Schneider-Electric iEM 2100 Series | ❌ | ✅ |
| Schneider-Electric iEM 2150 | ||
| Schneider-Electric iEM 2155 |

Bekabeling
De IEM 2100 serie communiceert via Modbus RTU over RS485.
Info
RS485 Wiring
- For correct RS485 wiring: Follow the guidelines for RS485 wiring.
- If the wiring shown in the table below is incorrect, please let us know.
- There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
| Device | Sofar EMS model OM1 | Sofar EMS model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| D1 (+) | RS485 A | RS485_POS | RS485 A | TX+ |
| D0 (-) | RS485 B | RS485_NEG | RS485 B | TX- |
| 0V / Shield | RS GND | GND | Not available | G |
Raadpleeg de handleiding van het apparaat voor de exacte pinnummers, aangezien deze licht kunnen variëren tussen specifieke submodellen (bijv. iEM2150 vs iEM2155).
Configuratie
Waarschuwing
NOTE: RS485 Device Addresses
- You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
- Use lower addresses first (1, 2, ...) because the Sofar EMS will find them faster!
- For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The Sofar EMS will scan on those first.
Communicatie Instellingen
Zorg ervoor dat de apparaatinstellingen overeenkomen met de hieronder gedefinieerde driverspecificaties:
- Baudrate: 9600, 19200 of 38400 (Standaard is vaak 19200)
- Pariteit: Even, Oneven of Geen
- Stopbits: 1
- Databits: 8