Sofar logo
Sofar logo
Accessoires
App
Apparaten
Cloud
Energie Meter
ABBAccuenergyAcrelAlgodueBijlageBMR
Carlo Gavazzi
ChargeeChintCloud Meter GegevensDornscheidt
Eastron
Eniris
FluviusFroniusHagerHomeWizardHuaweiIneproIskra
Janitza
JoulzKaifaKamstrupLandis+GyrLegrandLithiotM-BusMetcomP1ApiPhoenix-ContactPilootSagemcom
Schneider
Self configured energy meterSeneca S604SessyShelly energiemetersSiemensSmappeeSmartgrid-klaarSocomecSolax
Solis
Solis EnergiemeterSolis Netgekoppelde Energieteller
SunwodaTillquistVictronWeidmüllerYouLessZendure P1 MeterZiv
EV Laadstation
Gasmeter
Geschakelde Belastingen
Ketel
Nieuwe integraties
Plc
Pv hybride- en batterijomvormers
Warmtepomp
Watermeter
Bedradings- en verbindingsrichtlijnenCertificaten
Configuratie van A tot Z
EMS
Externe Signaleringen
Installatie
Klant specifiek
LicentieNetwerk
Probleemoplossing
Regeltijd reactieSnel aan de slagSpecificatiesStatus-LED'sVeiligheids-, onderhouds- en wettelijke mededelingen
ApparatenEnergie MeterSolis

Solis Energietellers

Solis

Ondersteunde apparaten

Device TypeModbus TCP (Ethernet)RS485
Solis Energy Meter✅✅
Autarco Energy Meter

Aansluiting

Ethernet

Voor correcte ethernetbekabeling: Volg de de richtlijnen voor ethernetbekabeling.

RS485

Info
RS485 Wiring
  • For correct RS485 wiring: Follow the guidelines for RS485 wiring.
  • If the wiring shown in the table below is incorrect, please let us know.
  • There is no general consensus in the industry about the usage of A and B for the RS485 polarity, so it may be counterintuitive and opposite of what you might expect for some devices.
DeviceSofar EMS model OM1Sofar EMS model IG8RS485-USB converterRS485-Ethernet converter
ARS485 ARS485_POSRS485 ATX+
BRS485 BRS485_NEGRS485 BTX-
GND (optional)RS GNDGNDNot availableG

Configuratie

Waarschuwing
NOTE: RS485 Device Addresses
  • You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
  • Use lower addresses first (1, 2, ...) because the Sofar EMS will find them faster!
  • For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The Sofar EMS will scan on those first.

Zorg dat de meter is geconfigureerd met de volgende Modbus-instellingen om te voldoen aan de driver-specificaties:

  • Baudrate: 9600
  • Databits: 8
  • Stopbits: 1
  • Pariteit: Geen
  • Modbus-adres: 1 (standaard) - Bereik: 1 tot 254