Sofar logo
Sofar logo
Accessoires
App
Apparaten
Cloud
Energie Meter
EV Laadstation
Gasmeter
Geschakelde Belastingen
Ketel
Nieuwe integraties
Plc
Pv hybride- en batterijomvormers
a-TroniXABB, FIMERADS-TecAforeAlphaESSAmpowrAngileAnklous PV-, Hybride- en BatterijomvormersAPsystemsAteps Batterij
Autarco
BeauventC-BatterijCellpowerChisageDanfossDeltaDET Power PV-, Hybride- en BatterijomvormersDEYEDiehl-AkoDMEGC OmvormersDynessDysun EnergyEcosourcenEenovanceElecnovaEnbrilionEnergreenEnerlutionEnjoyPowersEnphaseEP ApparatuurESY OmvormersEVEFortona
Foxess
FraxFroniusGoodWeGotionGroener / Alfen
Growatt
HiteHithium
Huawei
Hypontech
Hyxipower
iWellJinkoKacoKehuaKostal
Kstar
KSTAR BluE-S Serie (Gen 1)KSTAR BlueSpark-serie (Gen 2)KSTAR C&I Hybride Omvormers
MarstekMastervoltMidTeQMotomaOctave EnergyOmniPowerPixiiPower-SonicPoweroadPylontechRegitecRenonRenoverenRitarSAJSchneider SunEzySchucoSCUSE2200H tot SE6000HSessySigenergySinexcel
Sma
Socomec
Sofar
Solaredge
SolarlogSolarMaxSolarwattSolaxSolinteg
Solis
Solplanet
Sungrow
SunwaytechSunwoda
Sunwoda
Sus-PowerTeclomanTeploreTesvoltVaconVictronVolstoraWattsNextWeihengXantrexZendure SolarFlowZetaraZeversolar
Warmtepomp
Watermeter
Bedradings- en verbindingsrichtlijnenCertificaten
Configuratie van A tot Z
EMS
Externe Signaleringen
Installatie
Klant specifiek
LicentieNetwerk
Probleemoplossing
Regeltijd reactieSnel aan de slagSpecificatiesStatus-LED'sVeiligheids-, onderhouds- en wettelijke mededelingen
ApparatenPv hybride- en batterijomvormersKstar
logo

KSTAR BlueSpark Serie (Gen 2)

Let op
Let op

Een fout in eerdere versies van de KSTAR-integratie kon ervoor zorgen dat de batterij onder bepaalde omstandigheden onjuist met laden begon. Dit probleem is opgelost in versie 1.23.0.1. Werk je controller bij om deze bug te verhelpen.

Let op
Let op

Omdat de batterij in slaapstand gaat bij 10% SoC, raden we aan om het minimale laadniveau in te stellen op minstens 12%. Wanneer de batterij in slaapstand gaat, kan deze niet worden aangestuurd door de Sofar EMS.

Waarschuwing
Waarschuwing

Officiële KSTAR-documentatie bevestigt dat Modbus TCP (Ethernet) niet wordt ondersteund voor besturing door derden op deze apparaten. We raden aan om de KSTAR-batterij en de EMS met RS485 te verbinden.

Ondersteunde apparaten

Device TypeVariantsModbus TCP (Ethernet)RS485CurtailmentMinimum device firmware version
BlueSpark (2de Generatie) EnfaseE(3.68/5/6)KS-D22❌✅✅ARM v1.3.00 of hoger
BlueSpark (2de Generatie) DriefaseE(4/5/6/8/10/12)KT-D22Alle versies

Bekabeling

De Sofar EMS en de KSTAR-omvormers communiceren via RS485.

Enfase Bekabeling (E..KS-D22)

Verbind de EMS met de CT/METER-poort met een RS-485-kabel.

  • RS485-A: PIN 6
  • RS485-B: PIN 5
KSTAR connection diagram for single phase systems

Driefase Bekabeling (E..KT-D22)

Verbind de EMS met de METER/DRY-poort (specifiek de CT/METER-pinnen).

  • RS485-A: PIN 6
  • RS485-B: PIN 5
KSTAR connection diagram for three-phase systems

Configuratie

Waarschuwing
NOTE: RS485 Device Addresses
  • You MUST give each device on the RS485 bus a unique address. Check the manual of the device on how to do this.
  • Use lower addresses first (1, 2, ...) because the Sofar EMS will find them faster!
  • For each device, it is generally recommended to stick with the factory default baud rate, parity, and stop bits. The Sofar EMS will scan on those first.

Om ervoor te zorgen dat de EMS de omvormer kan aansturen, moeten de volgende instellingen op de omvormer via het scherm of de app worden aangepast.

1. Werkwijze-instellingen

Om VPP-besturing betrouwbaar te laten werken, moet u het volgende configureren:

  1. Stel Werkwijze in op Zelfconsumptie.
  2. Zet Opladen vanuit het net op Uitgeschakeld (binnen het Zelfconsumptiemenu).

2. Conflicterende modi uitschakelen

De volgende modi hebben een hogere prioriteit dan afstandsbediening en moeten worden Uitgeschakeld:

  • Forceer Laden/Ontladen (Instellen op "Ongeldig" of 0)
  • Generatormodus

3. Poortconfiguratie

Zorg ervoor dat de communicatiepoort correct is ingesteld:

  • CT/Meter selectie: Instellen op CT (standaard).
  • Baudrate: 9600.
Opmerking
Opmerking

Herstart de batterijomvormer na het wijzigen van de instellingen.