In beta and available on request. The additions in this overview require the matching integration or controller update and are not confirmed as part of the standard customer release. Request them through your existing Eniris support conversation. The status applies to these additions, not to every existing function of the devices listed elsewhere on this page.
| Model / system | Beta addition | Validation and conditions |
|---|---|---|
| ABB Terra AC | Identification when the serial-code response is empty | Bus-address fallback; commission the matching update |
See integration details for connection requirements and operating limitations.
| Device Type | Variants | Modbus TCP (Ethernet) | RS485 |
|---|---|---|---|
| ABB Terra AC | / | ✅ | ✅ |
For correct ethernet wiring: Follow the the guidelines for ethernet wiring.
| Device | Sofar EMS model OM1 | Sofar EMS model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| RS485 A | RS485_POS | RS485 A | TX+ | |
| RS485 B | RS485_NEG | RS485 B | TX- | |
| RS GND | GND | Not available | G |
After the electrical installation of a charger is complete, follow these steps to configure the charger:
Select "Local controller" and then "Modbus RTU (RS485)" or "Modbus TCP/IP" depending on whether the charging station is connected to the via RS485 or Ethernet.
Modbus RTU (RS485)
Choose a unique Modbus address, different from all other Modbus addresses of devices on the same RS485 bus.
Choose baud rate 9600, parity Even, stop bits 1 and data bits 8.
Modbus TCP/IP
You must set a fixed IP address in the charging station within the same network range as the.
Important: Always choose 502 as the server port.
For home and small business networks, a typical setup is with e.g. fixed IP address 192.168.1.50:
Terra AC detection can fall back to the bus address when the charger returns an empty serial code.