In beta and available on request. The additions in this overview require the matching integration or controller update and are not confirmed as part of the standard customer release. Request them through your existing Eniris support conversation. The status applies to these additions, not to every existing function of the devices listed elsewhere on this page.
| Model / system | Beta addition | Validation and conditions |
|---|---|---|
| CESC Mercury 261, protocol V2.0.1 | Battery/PCS monitoring and prepared power requests | Physical validation and power-sign check pending; no confirmed watchdog |
See integration details for connection requirements and operating limitations.
A custom integration is prepared for the Mercury 261 using protocol V2.0.1. Measurements use input registers and commands use holding registers, with one cabinet per unit address. Battery/PCS monitoring and active-power command logic are implemented.
Physical validation is pending. The protocol did not specify the charging sign unambiguously, so the implemented power direction must be verified before enabling control. No communication watchdog or documented return-to-local-strategy register is available in this mapping; releasing the prepared command writes zero power.