In beta and available on request. The additions in this overview require the matching integration or controller update and are not confirmed as part of the standard customer release. Request them through your existing Eniris support conversation. The status applies to these additions, not to every existing function of the devices listed elsewhere on this page.
| Model / system | Beta addition | Validation and conditions |
|---|---|---|
| ULTIBLOCK-TL261 | Separate cabinet protocol, TCP port 1502, unit 1 | Communication restored; full charge/discharge and limit validation pending |
See integration details for connection requirements and operating limitations.
A custom integration has been implemented for the ULTIBLOCK-TL261 cabinet. The verified device answers Modbus TCP on port 1502, unit ID 1; using port 1503 prevented discovery. This is a separate cabinet protocol, not the Ultimati hybrid-inverter connection. Communication has been restored; complete charge/discharge and operating-limit validation must be completed during commissioning.