In beta and available on request. The additions in this overview require the matching integration or controller update and are not confirmed as part of the standard customer release. Request them through your existing Eniris support conversation. The status applies to these additions, not to every existing function of the devices listed elsewhere on this page.
| Model / system | Beta addition | Validation and conditions |
|---|---|---|
| HYXiPOWER HYX-EF215P2-S | EMS monitoring and prepared remote/manual power control | Physical control commissioning required; use actual capacity and minimum SOC |
See integration details for connection requirements and operating limitations.
| Device Type | Variants | Manual | Modbus TCP (Ethernet) | RS485 | Curtailment | Reactive power control |
|---|---|---|---|---|---|---|
| All In One ESS | HYX-H6K-HTA | Manual | ❌ | ✅ | ✅ | — |
| HYX-H9K-HTA | ||||||
| HYX-H12K-HTA | ||||||
| HYX-H15K-HTA |
For RS485 Wiring, use the COM port (N° 5) on the inverter.
| Device | Sofar EMS model OM1 | Sofar EMS model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| RS485 A (Pin 5) | RS485 A | RS485_POS | RS485 A | TX+ |
| RS485 B (Pin 6) | RS485 B | RS485_NEG | RS485 B | TX- |
| N/A | RS GND | GND | Not available | G |
A custom cabinet integration reads the EMS at Modbus TCP unit ID 1 and prepares active-power control in remote/manual mode. Other cabinet sub-units are not treated as additional complete storage systems. Configure the actual installed capacity and the EMS minimum SOC; this integration does not invent absent alarm data from subordinate devices. Physical control validation remains installation-specific.